Close
LV426100 View larger

LV426100

Square D (Schneider Electric)

Square D (Schneider Electric)

3606481173461

New Factory Sealed - Original product -12 Months Warranty

Circuit breaker compact NSXm 16A 3P 16kA at 380/415V(IEC) EverLink lug

More details

1 Item

$272.51

Usually dispatched 1-2 days

Data sheet

Breaking Capacity Code Icu @ 415VE / 16kA
Poles Description3P
Trip Unit Rating16 A
Trip Unit NameTM-D
Connection TerminalsEverLink Lug

More info

Main
range
Compact
product name
Compact NSXm
device short name
NSXm 16E
product or component type
Circuit breaker
device application
Distribution
Protection
Complementary
[In] rated current
16 A
poles description
3P 3d
control type
Toggle
mounting mode
By screws for plate
Clip-on for DIN rail
network type
AC
network frequency
50/60 Hz
breaking capacity code
E
breaking capacity
25 kA at 220...240 V AC 50/60 Hz according to IEC 60947-2
16 kA at 380...415 V AC 50/60 Hz according to IEC 60947-2
10 kA at 440 V AC 50/60 Hz according to IEC 60947-2
8 kA at 500 V AC 50/60 Hz according to IEC 60947-2
[Ue] rated operational voltage
690 V AC 50/60 Hz according to IEC 60947-2
[Ics] rated service breaking capacity
25 kA at 220...240 V AC 50/60 Hz according to IEC 60947-2
16 kA at 380...415 V AC 50/60 Hz according to IEC 60947-2
10 kA at 440 V AC 50/60 Hz according to IEC 60947-2
8 kA at 500 V AC 50/60 Hz according to IEC 60947-2
[Uimp] rated impulse withstand voltage
8 kV according to IEC 60947-2
[Ui] rated insulation voltage
800 V according to IEC 60947-2
trip unit technology
Thermal-magnetic
trip unit name
TM-D
trip unit protection functions
LI
trip unit rating
16 A at 40 °C
protection type
Overload protection (thermal)
Short-circuit protection (magnetic)
long time pick-up adjustment range
0.7...1 x In
short-time pick-up adjustment type Isd
Fixed
short-time delay adjustment type
Fixed
magnetic hold current
400 A
magnetic tripping current
600 A
suitability for isolation
Yes according to IEC 60947-2
utilisation category
Category A
9 mm pitches
9 module
connection pitch
35 mm with spreaders
27 mm without spreaders
connections - terminals
1 Everlink lug 2.5...70 mm² (flexible) conductor :copper
1 Everlink lug 2.5...95 mm² (rigid or stranded) conductor :aluminium/copper
tightening torque
5 N.m for 2.5...10 mm²
9 N.m for 16...95 mm²
local signalling
Green flag for presence of auxiliary contacts
number of slots
1 slot(s) for auxiliary switch OF
1 slot(s) for alarm switch SD
1 slot(s) for voltage release MN or MX
wire stripping length
20 mm
Environment
quality labels
CE
standards
EN/IEC 60947
product certifications
CCC
EAC
Marine
colour
Grey (RAL 7016)
IP degree of protection
IP40 (front cover) according to IEC 60529
IK degree of protection
IK07 according to IEC 62262
pollution degree
3 according to IEC 60947-1
ambient air temperature for operation
-25...70 °C
ambient air temperature for storage
-40...85 °C
operating altitude
5000 m with derating
2000 m without derating
mechanical durability
20000 cycles according to IEC 947-1 Annex K ed 5.2 for In
electrical durability
10000 cycles according to IEC 947-1 Annex F ed 5.2 for In at 440 V
height
137 mm
width
81 mm
depth
80 mm
product weight
1.06 kg
quantity per set
Set of 1
Offer Sustainability
Sustainable offer status
Green Premium product
RoHS (date code: YYWW)
Compliant  - since  1649  -  Schneider Electric declaration of conformity Schneider Electric declaration of conformity
REACh
Product environmental profile
Product end of life instructions
Need no specific recycling operations

30 other products in the same category

Schneider Partner

Schneider Electric Authorised distributor

Shipping Partner

DHL Express Delivery

Secure Payments

Scure site globalsign

Close